| Parameter | Min | Typ | Max | Units | |
|---|---|---|---|---|---|
| Input Voltage Range | 90 | 528 | VAC | ||
| 100 | 745 | VDC | |||
| Input Type | Universal | ||||
| Input Frequency | 47 | 63 | Hz | ||
| Inrush Current | 115 VAC | 25 | A | ||
| 230 VAC | 40 | ||||
| Line Regulation | Full Load | ±0.5 | % | ||
| Load Regulation | % | ||||
| 0 to 100% Load | ±1 | ||||
| Hold-Up Time | 230 VAC | 35 | mSec | ||
| 400 VAC | 100 | ||||
| Isolation Voltage | 4,000 | VAC | |||
| Operating Temp Range | -40 | +70 | °C | ||
| MTBF | 300 | kHrs | |||
| Case Size | Without Chassis Mount | 2.441 x 1.772 x 1.181 | |||
| 62.00 x 45.00 x 30.00 | |||||
| With Chassis Mount | 3.783 x 2.126 x 1.516 | ||||
| 96.10 x 54.00 x 38.50 | |||||
| Package Type | Encapsulated Module | ||||
| Safety Class | |||||
| Safety Standards | See Model Selection Guide | ||||
| EMI/EMC Standards | Meets EN 55032 B |
| Model No. | Output V | Output I |
|---|---|---|
| MPM-10CW-03 | 3.3 VDC | 2000 mA |
| MPM-10CW-05 | 5 VDC | 2000 mA |
| MPM-10CW-09 | 9 VDC | 1100 mA |
| MPM-10CW-12 | 12 VDC | 900 mA |
| MPM-10CW-15 | 15 VDC | 700 mA |
| MPM-10CW-24 | 24 VDC | 450 mA |