| Parameter | Min | Typ | Max | Units | |
|---|---|---|---|---|---|
| Input Voltage Range | |||||
| AC Input | 90 | 264 | VAC | ||
| DC Input | 120 | 370 | VDC | ||
| Input Type | Universal | ||||
| Input Frequency | 47 | 63 | Hz | ||
| Inrush Current(Cold Start) | 115 VAC | 20 | |||
| 230 VAC | 40 | A Pk | |||
| Power Factor(Full Load) | 115 VAC | 0.99 | |||
| 230 VAC | 0.95 | ||||
| Line Regulation(At Rated Load) | Main Output | ±0.5 | % | ||
| Auxiliary Output | ±1.0 | ||||
| Load Regulation(5 - 100% Load) | Main Output | ±0.5 | |||
| Auxiliary Output | ±1.0 | % | |||
| Hold-Up Time | 115 VAC | 12 | mSec | ||
| 230 VAC | 12 | ||||
| Isolation Voltage | 4000 | VAC | |||
| Operating Temp Range | -40 | +70 | °C | ||
| MTBF | 250 | kHrs | |||
| Case Size | in | 7.283 x 5.00 x 1.594 | |||
| mm | 185.0 x 127.0 x 40.50 | ||||
| Package Type | Enclosed Module | ||||
| Safety Class | Class I | ||||
| Safety Standards | UL/cUL 62368-1 Recognition (UL Certificate) | ||||
| EMI/EMC Standards | Meets EN 55032 B |
| Model No. | Output V | Output I |
|---|---|---|
| MPE-1000CM-12 | 12 VDC | 80 A |
| MPE-1000CM-15 | 15 VDC | 64 A |
| MPE-1000CM-24 | 24 VDC | 42 A |
| MPE-1000CM-27 | 27 VDC | 37.3 A |
| MPE-1000CM-36 | 36 VDC | 28 A |
| MPE-1000CM-48 | 48 VDC | 21 A |
| MPE-1000CM-54 | 54 VDC | 18.7 A |