MDR-960HY

Key Features

  • 960W Output Power
  • 3 kVAC I/O Isolation
  • UL Approved
  • -30°C to 70°C Operation
  • >82 kHour MTBF
  • Meets EN 55032 B
  • Takes AC or DC Input
  • DC OK Relay Contact
  • OVC II

Datasheet

Additional Tech Info

ParameterMinTypMaxUnits
Input Voltage Range90264VAC
254370VDC
Input TypeUniversal
Input Frequency4763Hz
Inrush Current(Cold Start)A Pk
230 VAC50
Line Regulation±0.5%
Load Regulation±1.0%
Hold-Up Time(Full Load)14mSec
Isolation Voltage3,000VAC
Operating Temp Range-30+70°C
MTBF82kHrs
Case Size4.90 x 4.33 x 5.91
124.7 x 110.0 x 150.2
Package TypeDIN-Rail
Safety ClassClass I
Safety StandardsUL 61010-1, UL 61010-2-201
EMI/EMC StandardsCISPR 32 / EN 55032
Model No.Output VOutput I
MDR-960HY-2424 VDC40 A
MDR-960HY-4848 VDC20 A