MDR-60SY

Key Features

  • 60W Output Power
  • 4 kVAC I/O Isolation
  • UL Approved
  • -20°C to 70°C Operation
  • >300 kHour MTBF
  • Meets EN 55032 B
  • Takes AC or DC Input
  • Adjustable DC Output

Datasheet

Additional Tech Info

RoHS CE UK UL
ParameterMinTypMaxUnits
Input Voltage Range90264VAC
127370VDC
Input TypeUniversal
Input Frequency4763Hz
Inrush Current115 VAC30Apk
230 VAC60
Line RegulationAt Rated Load±1.0%
Load Regulation230 VAC 0 - 100% Load±1.0%
Hold-Up Time115 VAC12mSec
230 VAC30
Isolation Voltage4,000VAC
Operating Temp Range-20+70°C
MTBF300kHrs
Case Size3.648 x 2.047 x 2.28
92.66 x 52.0 x 58.0
Package TypeEncapsulated Module
Safety ClassClass II
Safety StandardsUL 62368-1
EMI/EMC StandardsCISPR 32 / EN 55032
Model No.Output VOutput I
MDR-60SY-0554.5 A
MDR-60SY-12124.5 A
MDR-60SY-15154.0 A
MDR-60SY-24242.5 A
MDR-60SY-48481.25 A