MDR-30SP

Key Features
- 30W Output Power
- 4,000 VAC I/O Isolation
- DIN Rail TS35 (7.5 or 15) Mountable
- UL/cUL 62368 Approved
- Universal 85-264 AC Input
- Only 35 mm (2 SU) Wide
- Meets EN 55032 B
- Meets LPS (Limited Power Source)
- Meets OVC III (EN 61558)
- -40°C to +70°C Operation
Datasheet
Additional Tech Info

Parameter | Min | Typ | Max | Units | |
---|---|---|---|---|---|
Input Voltage Range | 85 | 264 | VAC | ||
Input Type | Universal | ||||
Input Frequency | 47 | 63 | Hz | ||
Inrush Current | 115 VAC | 24 | APk | ||
230 VAC | 45 | ||||
Line Regulation | ±0.5 | % | |||
Load Regulation | ±1.5 | % | |||
Hold-Up Time, 115 VAC 230VAC | 12 60 | mSec | |||
Isolation Voltage | 4,000 | VAC | |||
Operating Temp Range | -40 | +70 | °C | ||
MTBF | 300 | kHrs | |||
Case Size (with mount) | 1.387 x 3.54 x 2.28 In | ||||
35.0 x 90.0 x 58.0 mm | |||||
Package Type | DIN Rail | ||||
Safety Standards | UL/cUL 62368 Approved |
||||
Safety Class | Class II | ||||
Overvoltage Class | Class III (EN 61558) | ||||
EMI/EMC Standards | EN 55032, EN 61000 |
Model No. | Output V | Output I |
---|---|---|
MDR-30SP-05 | 5.0 VDC | 3.00 A |
MDR-30SP-12 | 12 VDC | 2.00 A |
MDR-30SP-15 | 15 VDC | 2.00 A |
MDR-30SP-24 | 24 VDC | 1.50 A |
MDR-30SP-48 | 48 VDC | 0.75 A |