| Parameter | Min | Typ | Max | Units | |
|---|---|---|---|---|---|
| Input Voltage Range | 90 | 264 | VAC | ||
| 127 | 370 | VDC | |||
| Input Type | Universal | ||||
| Input Frequency | 47 | 63 | Hz | ||
| Inrush Current(Cold Start) | 115 VAC | 20 | A Pk | ||
| 230 VAC | 35 | ||||
| Line Regulation | ±0.5 | % | |||
| Load Regulation | ±1.0 | % | |||
| Hold-Up Time(Full Load) | 115 VAC/60Hz | 12 | mSec | ||
| 230 VAC/50Hz | 16 | ||||
| Isolation Voltage | 3,000 | VAC | |||
| Operating Temp Range | -20 | +70 | °C | ||
| MTBF | 200 | kHrs | |||
| Case Size | 4.92 x 2.48 x 4.47 | ||||
| 125.0 x 63.0 x 113.5 | |||||
| Package Type | DIN-Rail | ||||
| Safety Class | Class I | ||||
| Safety Standards | UL508, EN62368-1 | ||||
| EMI/EMC Standards | CISPR 32 / EN 55032 |
| Model No. | Output V | Output I |
|---|---|---|
| MDR-240SNY-24 | 24 VDC | 10 A |
| MDR-240SNY-48 | 48 VDC | 5 A |