Parameter | Min | Typ | Max | Units | |
Input Voltage Range | 85 | 264 | VAC | ||
120 | 370 | VDC | |||
Input Type | Universal | ||||
Input Frequency | 47 | 63 | Hz | ||
Inrush Current | 115 VAC | 30.0 | APk | ||
220 VAC | 60.0 | ||||
Line Regulation | ±0.5 | % | |||
Load Regulation | ±1.0 | % | |||
Hold-Up Time, 220 VAC | 22 | mSec | |||
Isolation Voltage | 3,000 | VAC | |||
Operating Temp Range | -25 | +70 | °C | ||
MTBF | 200 | kHrs | |||
Case Size | 4.74 x 2.36 x 4.92 In | ||||
120.0 x 60.0 x 125.0 mm | |||||
Package Type | DIN Rail Mount | ||||
Safety Standards | EN 60950, UL 60950 | ||||
EMI/EMC Standards | EN 55022, EN 61000-4 | ||||
Model No. | Output V | Output I |
MDR-240S-24 | 24.0 VDC | 10.0 A |